Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1209753.015
Citation: 01001
Citation Type: Serious
Abatement Date: 05/16/2017 2
Initial Penalty: $1,386.00
Current Penalty: $1,386.00
Issuance Date: 04/20/2017
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0729700
Contest Date:
Final Order: 05/16/2017
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 04/20/2017 | $1,386.00 | 05/16/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(g)(1)(i)(A): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized shall comply with the following dimensions, except as required or permitted elsewhere in this subpart: In the shop, the depth of the working space in the direction of access to the breaker box located to the rear of the air compressor was less than indicated in Table S-1 (three feet is minimum). Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed. Employees were exposed to a shock hazard and or the hazard of contacting the nip-points through the holes in the compressor guarding.