Violation Detail
Standard Cited: 19100333 B02 II B Selection and use of work practices
Inspection Nr: 1204127.015
Citation: 01003
Citation Type: Serious
Abatement Date: 06/29/2017 2
Initial Penalty: $6,926.00
Current Penalty: $6,926.00
Issuance Date: 06/19/2017
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC): A;R
Gravity: 5
Report ID: 0627500
Contest Date:
Final Order: 08/01/2017
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 06/19/2017 | $6,926.00 | 06/29/2017 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.333(b)(2)(ii)(B): Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for de-energizing circuits and equipment: At the substation: On or about January 19, 2017, the employer used the selector switch on the VISTA distribution switchgear as the sole means for de-energizing electrical equipment. The distribution switchgear was de-energized on the out-going side, but remained energized on the in-coming side. Employees were exposed to electrical hazards.
Translate