Violation Detail
Standard Cited: 19100303 G01 General.
Inspection Nr: 1194248.015
Citation: 01011
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $3,532.00
Current Penalty: $3,000.00
Issuance Date: 02/27/2017
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 03/29/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/29/2017 | $3,000.00 | Serious | ||
Penalty | Z: Issued | 02/27/2017 | $3,532.00 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Walk-On Ceiling, Mechanical Room: On, or about, December 6, 2016, electrical conduit had been installed in front of the electrical panels located in the room. The conduit created a tripping hazard, created a path to ground and could have been damaged by being stepped on. The presence of the conduit impeded access to the panels.