Violation Detail
Standard Cited: 19260403 B02 General requirements.
This violation item has been deleted.
Inspection Nr: 1185526.015
Citation: 01002
Citation Type: Serious
Abatement Date: 04/04/2017
Initial Penalty: $12,675.00
Current Penalty: $0.00
Issuance Date: 03/09/2017
Nr Instances: 1
Nr Exposed: 15
Related Event Code (REC): A
Gravity: 10
Report ID: 0316700
Contest Date:
Final Order: 03/27/2017
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/27/2017 | $0.00 | 04/04/2017 | Serious | |
| Penalty | Z: Issued | 03/09/2017 | $12,675.00 | 04/04/2017 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) Building I2, Mezzanine Level; Switchgear S&T - On or about October 19, 2016 and times prior thereto, a distribution feeder was used as a tie circuit breaker within a double-ended substation. Employees were exposed to electrocution hazards while working in switchgear S&T. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.