Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1118265.015
Citation: 01022
Citation Type: Other
Abatement Date: 07/14/2016 2
Initial Penalty: $5,000.00
Current Penalty: $2,000.00
Issuance Date: 07/08/2016
Nr Instances: 2
Nr Exposed: 308
Related Event Code (REC):
Gravity:
Report ID: 0625400
Contest Date:
Final Order: 07/29/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/29/2016 | $2,000.00 | 07/14/2016 | Other | |
Penalty | Z: Issued | 07/08/2016 | $5,000.00 | 07/14/2016 | Serious |
Text For Citation: 01 Item/Group: 022 Hazard:
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy. On or about 13 January 2016, and at times prior thereto, electrical outlets located in walls as completed installations did not have the faceplate, exposing employees to an electrical hazard of approximately 120 volts. A) Conference Room: On the east wall, the two-plug outlet was missing the faceplate. The outlet was energized at the time of the inspection. B) Small Break Room: On the south wall, the two-plug outlet was missing the faceplate. The outlet was energized at the time of the inspection. Also, the west and north walls both had two-plug outlets that had damage to the faceplates, but not to the extent the terminals or wires were visible.