Violation Detail
Standard Cited: 19100305 J02 IV Wiring methods, components, and equipment for general use.
Inspection Nr: 1109295.015
Citation: 01023
Citation Type: Serious
Abatement Date: 03/02/2016 2
Initial Penalty: $2,800.00
Current Penalty: $600.00
Issuance Date: 02/16/2016
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC):
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 03/16/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/16/2016 | $600.00 | 03/02/2016 | Serious | |
Penalty | Z: Issued | 02/16/2016 | $2,800.00 | 03/02/2016 | Serious |
Text For Citation: 01 Item/Group: 023 Hazard:
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: The employer had the following receptacles installed in a wet/damp location which was not suitable for the location: a. The receptacle outlet fixtures along the CNC wall, on the west side of the main building were exposed to wet/damp locations during rain. Employees had used the receptacles to plug in fans. b. The receptacles in the paint room were used to power extension cords, sanders, and spray painting guns. The receptacles were exposed to wet/damp locations from the painting process and were not suitable for the location.