Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 108974.015
Citation: 01002
Citation Type: Other
Abatement Date: 01/31/2012 2
Initial Penalty: $1,800.00
Current Penalty: $400.00
Issuance Date: 01/27/2012
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity:
Report ID: 0522000
Contest Date:
Final Order: 02/08/2012
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/08/2012 | $400.00 | 01/31/2012 | Other | |
| Penalty | Z: Issued | 01/27/2012 | $1,800.00 | 01/31/2012 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) On or about November 14, 2011, the 200-Amp feeder electric breaker panel located outside the Boiler Room and the wall-mounted branch circuit breaker panel located inside the boiler room did not have the over current breaker devices in each panel labeled to identify to its service location.