Violation Detail
Standard Cited: 19100107 L07 V Spray finishing using flammable and combustible materials.
Inspection Nr: 1081797.015
Citation: 01005
Citation Type: Serious
Abatement Date: 03/04/2016 2
Initial Penalty: $4,500.00
Current Penalty: $2,925.00
Issuance Date: 01/15/2016
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): C
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 02/09/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/09/2016 | $2,925.00 | 03/04/2016 | Serious | |
Penalty | Z: Issued | 01/15/2016 | $4,500.00 | 03/04/2016 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.107(l)(7)(v): The electrical equipment was not interlocked with the ventilation system so that the equipment could not be operated unless the ventilation fans were in operation: SPRAY BOOTH On, or about, July 30, 2015, the spray guns were not interlocked with the ventilation system and were operable when the fans were off. Employees used coatings such as, but not limited to, 4th Dimension Basecoat, product number 5B, a flammable coating, with a flash point of 50 F.