Violation Detail
Standard Cited: 19260405 B02 Wiring methods, components, and equipment for general use.
Inspection Nr: 1049365.015
Citation: 01001A
Citation Type: Serious
Abatement Date: 04/09/2015 2
Initial Penalty: $1,600.00
Current Penalty: $800.00
Issuance Date: 04/01/2015
Nr Instances: 4
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0111100
Contest Date:
Final Order: 04/20/2015
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/20/2015 | $800.00 | 04/09/2015 | Serious | |
| Penalty | Z: Issued | 04/01/2015 | $1,600.00 | 04/09/2015 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy: a) Room on southwest side of the North Commons - A cover was not provided on a permanently installed junction box which provided power to a temporary light and to a ground fault protected receptacle box mounted on a portable stand. b) Northeast wall of North Commons - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected portable receptacle box. c) Northeast wall of North Commons - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected portable receptacle box. d) Hall on south end of building - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected receptacle box mounted on a portable stand.