Violation Detail
Standard Cited: 19100305 G01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1018907.015
Citation: 01006
Citation Type: Serious
Abatement Date: 08/11/2015 3
Initial Penalty: $2,000.00
Current Penalty: $1,500.00
Issuance Date: 07/09/2015
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0418100
Contest Date:
Final Order: 07/17/2015
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/17/2015 | $1,500.00 | 08/11/2015 | Serious | |
| Penalty | Z: Issued | 07/09/2015 | $2,000.00 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.305(g)(1)(i): Flexible cords and cables were not approved for conditions of use and location: a) Yard, Gang Saw Area - On or about 01/13/15 and at times prior thereto employees operated the gang saw and the cart to transport marble slabs to the yard. The male-female plug in the 480 V flexible power cable for the cart was exposed to water during the wet cutting process inside the saw, and while situated outdoors. The plug was not designed for contact with water, and employees were exposed to the accidental electrification of the cart. b) Yard, Gang Saw Area - On or about 01/13/15 and at times prior thereto the 480 V flexible power cable for the cart was exposed to abrasion and damage caused by the sharp edges of the metallic wall of the cart. Employees were exposed to electrical discharges due to the accidental electrification of the cart. Abated during the inspection. No abatement certification is required.
Translate