Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1017207.015
Citation: 01007B
Citation Type: Serious
Abatement Date: 07/24/2015 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/29/2015
Nr Instances: 3
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0213900
Contest Date:
Final Order: 07/15/2015
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/15/2015 | $0.00 | 07/24/2015 | Serious | |
| Penalty | Z: Issued | 06/29/2015 | $0.00 | 07/24/2015 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) Repair Shop, east wall: Employees were exposed to trip hazards due to the work space in front of D-square knife switch powering the shops exhaust fan not being clear. A file cabinet was stored in the work space in front of the switch. Observed on or about 03/16/2015. b) Repair Shop, east wall: Employees were exposed to trip hazards due to the work space in front of a circuit breaker panel powering the shops power outlets not being clear. A large industrial scale was stored in the work space in front of the panel. Observed on or about 03/16/2015. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.