Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1726000.015
Citation: 01005
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/30/2024
Nr Instances: 3
Nr Exposed: 18
Abatement Date:
Gravity: 5
Report ID: 0111100
Contest Date:
Final Order: 08/26/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 07/30/2024 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and/or branch circuit at its disconnecting means or overcurrent device was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: 401 West Main Street Facility - On, or about, February 2, 2024 it was found that circuit breakers were not labeled, in the following instances: a) Boiler Room - Panel DP-1, Breaker 22. b) LAN Room - Panel L, Breakers 6 & 8. c) Large Port of Entry Booth - Breakers 28, 30, & 35, and double breakers 32/34 & 31/33.