Violation Detail
Standard Cited: 19260152 D02 Flammable liquids.
Inspection Nr: 1500381.015
Citation: 01002
Citation Type: Serious
Abatement Date: 03/09/2021 2
Initial Penalty: $2,340.00
Current Penalty: $1,755.00
Issuance Date: 02/10/2021
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity: 1
Report ID: 0317700
Contest Date:
Final Order: 03/02/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/02/2021 | $1,755.00 | 03/09/2021 | Serious | |
Penalty | Z: Issued | 02/10/2021 | $2,340.00 | 03/09/2021 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1926.152(d)(2): A portable fire extinguisher having a rating of not less than 20-B units was not located between 25 feet and 75 feet from flammable liquid storage area(s) located outside: a) Danville, PA: A portable fire extinguisher was not provided for the refueling area, which contained two large diesel storage tanks, observed on November 2, 2020. ABATEMENT CERTIFICATION REQUIRED