Inspection Detail
Inspection: 115937351 - Williams Electric
Inspection Information - Office: Ky Labor Cabinet Division Of Osh Compliance
Site Address:
Williams Electric
Salyersville Health Care Center
Salyersville, KY 41465
Mailing Address:
Box 335, Salyersville, KY 41465
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/29/1991
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/19/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361067119 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $280 | $0 | $0 | $0 | $0 | $280 |
| Current Penalty | $280 | $0 | $0 | $0 | $0 | $280 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 338003101 A | 10/22/1991 | 10/28/1991 | $280 | $280 | $0 | 12/24/1991 | R - Review Commission | |
| 2. | 01001B | Serious | 19260200 H01 | 10/22/1991 | 10/28/1991 | $0 | $0 | $0 | 12/24/1991 | R - Review Commission |
Investigation Summary
TWO EMPLOYEES, AN ELECTRICIAN AND HIS ASSISTANT, WERE REINSTALLING AN INDUSTRIAL DISHWASHER DURING THE RENOVATION OF A KITCHEN. THE ELECTRICIAN WAS CONNECTING THE CONDUCTORS OF THE DISHWASHER TO THE 480-VOLT, 3-PHASE SUPPLY. THREE SEPARATE CIRCUIT BREAKERS CONTROLLED THE DISHWASHER CIRCUITS. ALL THREE HAD BEEN TAPED IN THE OPEN POSITION WITH ELECTRICAL TAPE; AND, BEFORE WORKING ON THE EQUIPMENT, THE EMPLOYEES TESTED THE SUPPLY CONDUCTORS AND FOUND THEM TO BE DEENERGIZED. THE ELECTRICIAN HAD FINISHED CONNECTING TWO OF THE CIRCUITS WHEN THE ASSISTANT LEFT FOR ABOUT 15 MINUTES TO RETRIEVE PARTS. UPON THE ASSISTANT'S RETURN, THE ELECTRICIAN STARTED WORKING AGAIN AND WAS ELECTROCUTED. THE THIRD CIRCUIT BREAKER HAD HAD ITS TAPE REMOVED AND WAS REENERGIZED. THERE WERE OTHER CONTRACTORS AND EMPLOYEES NEARBY, BUT IT WAS NOT DISCOVERED HOW THE TAPE WAS REMOVED OR HOW THE BREAKER WAS REENERGIZED.
Keywords: ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 115937351 | Fatality | Electric Shock | Electricians |
Translate