Accident: 111668.015 - Employee Contacts Dc Batteries And Is Electrocuted

Accident: 111668.015 -- Report ID: 0316400 -- Event Date: 12/04/2018
InspectionOpen DateSICEstablishment Name
1364871.01512/04/2018Empower Battery, Llc

At 11:37 a.m. on December 4, 2018, an employee was replacing 640 batteries in th e facilities uninterrupted power supply (UPS) room. The batteries were linked in 16 strings with each string having 40 batteries tied in series. Each string wa s 540V and 2280 amps. The employee reached overtop of a metal batter rack to r etrieve a Styrofoam spacer and his abdomen came in contact with the string of ba tteries below. The employee was electrocuted.

Keywords: battery, electrocuted

Employee Details
Employee # Inspection Age Sex Degree Nature Occupation
1 1364871.015 29 M Fatality Electrical and electronic technicians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.