Accident Report Detail
Accident Summary Nr: 102226.015 - Employee contacts an overhead power line and is electrocuted
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1287806.015 | 01/11/2018 | 238140 | Robert Sean Looney |
Abstract: At 1:05 p.m. on January 10, 2018, an employee and coworkers were erecting a tubular welded frame scaffold in front of a commercial building in order to repair the top four feet of brick at the front of the building. The scaffold was erected four tiers high, near an energized, uninsulated power line (13.2 kV phase to phase). The minimum required clearance distance of 10 feet was not maintained. As the construction of the scaffold was almost complete with only the last few pieces of guardrail to be installed, the employee inadvertently contacted the power line with a 7-foot long piece of metal scaffolding. The employee was electrocuted as a result.
| End Use | Project Type | Project Cost | Stories | Non-building Height | Fatality | ||
|---|---|---|---|---|---|---|---|
| Commercial building | Maintenance or repair | X | |||||
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation | Construction |
|---|---|---|---|---|---|---|---|
| 1 | 1287806.015 | 21 | M | Fatality | Construction laborers | Distance of Fall: feet Worker Height Above Ground/Floor: feet Cause: Exterior masonry Fatality Cause: |