Regulations (Standards - 29 CFR)
Audiometric test rooms - 1910.95 App D |
|
|
| Part Number: | 1910 |
| Part Title: | Occupational Safety and Health Standards |
| Subpart: | G |
| Subpart Title: | Occupational Health and Environment Control |
| Standard Number: | 1910.95 App D |
| Title: | Audiometric test rooms |
|
This Appendix is Mandatory Rooms used for audiometric testing shall not have background sound pressure levels exceeding those in Table D-1 when measured by equipment conforming at least to the Type 2 requirements of American National Standard Specification for Sound Level Meters, S1.4-1971 (R1976), and to the Class II requirements of American National Standard Specification for Octave, Half-Octave, and Third-Octave Band Filter Sets, S1.11-1971 (R1976).
TABLE D-1 - MAXIMUM ALLOWABLE OCTAVE-BAND SOUND PRESSURE LEVELS
FOR AUDIOMETRIC TEST ROOMS
_______________________________________________________________
Octave-band center
frequency (Hz)............... 500 1000 2000 4000 8000
Sound pressure level (dB) ... 40 40 47 57 62
_______________________________________________________________
|
|
|
|
|