| Standard Number: | 1926.152 |
|
June 11, 1996
Mr. Ted Hillman Dear Mr. Hillman: This is in response to your request for an interpretation of the Occupational Safety and Health Administration standards addressing fire protection during the fueling of mobile equipment (1926.152(g)(10)). We appreciated the opportunity to meet with you to discuss the Wiggins Dry Break Connection and Automatic Fuel Shutoff System. As discussed in our meeting, the requirement to shut off the engines of mobile equipment during the fueling operation is intended to prevent injuries due to fire. We agree that if the equipment is equipped with a Wiggins Refueling System, and the equipment is refueled outdoors or in a well ventilated open structure, the intent of §1926.152(g)(10) is met and that conducting diesel fueling operations with the engine running would be a de minimis condition. This de minimis situation applies only when using diesel fuel. As you know, de minimis conditions are violations which have no direct or immediate relationship to safety or health and are not included in citations. If you require any further assistance, please do not hesitate to contact the Directorate of Construction again. Sincerely,
Roy F. Gurnham, P.E., J.D. |
|
|