December 30, 1983 Gerald M. Brown Lieutenant-Fire Department Buick Motor Division 902 E. Hamilton Avenue Flint, Michigan 48550 Dear LT. Brown: This is in response to your letter of December 5, 1983, requesting a clarification of 29 CFR 157(f)(16). For the clarification requested, 29 CFR 157(f)(16) pertinently states: "Such evidence shall include the date of test, the test pressure used, and the person or agency performing the test." To be complete, your computer printout for the stored pressure water and dry chemical extinguishers lacks, in its listing, the test pressure used and person or agency performing the test. However, if evidence is otherwise maintained for these two non-listed items, then the evidence would be complete as required by 29 CFR 157(f)(16). For your carbon dioxide extinguishers tested by a contract vendor, the employer shall have the date of test, the test pressure used and the person or agency performing the test for each of the carbon dioxide extinguishers. Should you have any further questions, please do not hesitate to contact us. Sincerely, John F. Miles, Jr., Director Directorate of Field Operations |