| Standard Number: | 1910.158 |
|
November 16, 1982
Mr. Paul R. Kaveler Dear Mr. Kaveler: This is in response to your letter of October 26, 1982, requesting a clarification of several items in Subpart L of the General Industry Safety and Health Standards. My response to your three questions follows: 1. The manufacturer's acceptance test conducted at the factory does satisfy 29 CFR 1910.158(e)(ii), providing the test of the hose is conducted with the couplings attached. 2. Subpart L does not require any periodic hydrostatic testing of fire hose, but we do require that the hose be inspected annually and maintained in serviceable condition. 3. It was not the intent of 29 CFR 1910.158(e)(ii) to specifically cross-reference with NFPA Standards 1962 - 1979. If I may be of further assistance, please feel free to contact me.