| Standard Number: | 1910.104 |
|
July 23, 1981
Bernard J. Wilkes, III Dear Mr. Wilkes: Mr. Hillenbrand has asked me to respond to your letter of June 29, 1981, regarding a bulk oxygen system at the Southwest Steel Company at Grafton, West Virginia. A liquid oxygen storage system of 1200-1300 gallons is equivalent to a storage system of more than 130,000 cubic feet at normal temperature and pressure (NTP) and is therefore classified as a bulk oxygen system per 29 CFR 1910.104(b)(1). The requirements of that standard appear to be applicable to your situation. Since OSHA conducted no inspection of the circumstances in question, we are unable to provide you with further assistance or guidance at this time. If we may be of further assistance, please call or write.