| Standard Number: | 1910.106 |
|
September 8, 1976
Mr. Kenneth Koning, RE: Your letter dated August 6, 1976 - 1910.106, Flammable and Combustible Liquids Dear Mr. Koning: In 1910.106(d)(4), Design and construction of inside storage rooms, we find the following: (i) Construction. Inside storage rooms shall be constructed to meet the required fire-restrictive rating for their use. Such construction shall comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969, etc. The construction proposed by your assured must comply with the above cited requirements. Exposed steel trusses and metal decking is not rated as fire resistive construction. When the room is constructed to comply with the above requirements, the restrictions of Table H-13 will still apply. Please contact us if we can be of further service. You may call toll-free at 800-621-0523.