| Standard Number: | 1910.106(d)(5)(vi)(e) |
|
September 2, 1975
Mr. E.F. Makin Dear Mr. Makin: Your letter dated August 20 regarding storage of flammable liquids was referred to this office for reply. The "obstructions" mentioned in 29 CFR [1910.]106(d)(5)(vi)(e) are those that would impede the flow of water from sprinklers or hose streams when combating fires. Space between containers of flammable liquids and a wall is required only when the material is subject to expansion when wet with water. Metal containers of flammable liquids do not require a wall aisle. Sincerely yours,
David H. Rhone |
|
|