Powered by GoogleTranslate

Citation 306798679/01001

InspectionReporting IDOpen DateSICEstablishment Name
306798679 0521100 02/11/2005 1623Wisconsin Public Service

CitationIssuance DateHazard Category
01001 05/09/2005 Electric

Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical arc flash: a) At the Weston WPS Power Plant #4, an arc flash hazard analysis was not conducted. Employees, were working within the flash boundary (that was not determined prior to exposure) while testing on an energized 6.9KV primary/480V secondary panel board without the appropriate personal protective clothing or equipment and were exposed to the hazard of electrical burns due to arc flash. Among feasible means of abatement would be to comply with the 2004 Edition of the National Fire Protection Association (NFPA) 70E, Standard for Electrical Safety in the Workplace, Article 130, Section 130.3 Flash Hazard analysis: to determine the flash protection boundary, Article 110, Section 110.7(G) Job Briefing: covers hazards associated with the job, work procedures involved. Abatement Certification or Abatement Documentation required.tion

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close