29 CFR 1910.119(d)(2)(i)(D): Process safety information pertaining to the technology of the process did not include the safe upper and lower limits for such items as temperatures, pressures, flows or compositions: a.BP-Husky Refining, LLC - Oregon, Ohio: On or about September 10, 2009, the employer did not ensure heat transfer information for the refractory lined FCC Reactor (PR 511024), located in the FCC unit, were calculated to determine the vessel wall temperatures in comparison with the design metal temperatures when operating at the maximum internal temperature of 1050 degrees F. b.BP-Husky Refining, LLC - Oregon, Ohio: On or about September 10, 2009, the employer did not ensure heat transfer calculations for the refractory lined FCC Regenerator (PR 511023), located in the FCC unit, were calculated to determine the vessel wall temperatures in comparison with the design metal temperatures when operating at the maximum internal temperature 1400 degrees F. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
|