<< Back to Chemical Sampling Information
|
Chemical Sampling Information (CSI)
|
|
|
| Search (use word(s)/phrase) |
|
|
|
Table of Contents
|
|
|
|
|
|
|
Quick Links
|
|
|
|
|
Diethylamine
OSHA IMIS Code Number: 0910
Chemical Abstracts Service (CAS) Registry Number: 109-89-7
NIOSH Registry of Toxic Effects of Chemical Substances (RTECS) Identification Number: HZ8750000; 31431
Department of Transportation Regulation Number (49 CFR 172.101) and Guide: UN1154 Flammable Liquid
Chemical Description and Physical Properties:
colorless liquid with ammonia-like odor
molecular weight: 73
boiling point: 132°F
vapor pressure: 195 mm
melting point: -58°F
Incompatibilities: Strong oxidizers and acids
OSHA Permissible Exposure Limit (PEL):
General Industry: 25 ppm, 75 mg/m3
Construction Industry: 25 ppm, 75 mg/m3 TWA
American Conference of Governmental Industrial Hygienists (ACGIH) Threshold Limit Value (TLV): 5 ppm, 15 mg/m3 TWA; 15 ppm, 45 mg/m3 STEL (Skin) A4 (Not Classifiable as a Human Carcinogen)
National Institute for Occupational Safety and Health (NIOSH) Recommended Exposure Limit (REL): 10 ppm TWA, 25 ppm STEL
Potential Symptoms: Eye, skin, respiratory irritation
Health Effects: Irritation-Eye, Nose, Throat, Skin---Marked (HE14) Myocardial degeneration (HE3)
Affected Organs: Respiratory system, skin, eyes
NIOSH/OSHA/DOE Health Guideline: Diethylamine
Primary Laboratory Sampling/Analytical Method (SLC1):
-
sampling media: Coated XAD-7 tube (80/40 mg sections, 20/50 mesh); coating is 10% (w/w) NBD-Chloride
analytical solvent: Tetrahydrofuran
maximum volume: 10 Liters
maximum flow rate: 0.2 L/min (TWA)
maximum volume: 3 Liters
maximum flow rate: 0.2 L/min (STEL)
current analytical method: High Performance Liquid Chromatography; HPLC/FLU/VIS
method reference: 2 OSHA 41
sampling and analytical error: 0.12
method classification: Fully Validated
-
sampling media: Coated XAD-2 tube (80/40 mg sections, 20/50 mesh); coating is 10% 1-Naphthylisothiocyanate
analytical solvent: Dimethylformamide
maximum volume: 10 Liters
maximum flow rate: 0.2 L/min (TWA)
maximum volume: 3 Liters
maximum flow rate: 0.2 L/min (STEL)
current analytical method: High Performance Liquid Chromatography; HPLC/UL58
method classification: Fully Validated
method reference: 2 (OSHA In-house file)
method classification: Partially Validated
Conditions: Column: CN Mobile Phase: 80:20 Isooctane: IPA Detector Wavelength: 465 EX: 525 EM (Fluor) Detection Limit: 1.6 ug/sample
Secondary Laboratory Sampling/Analytical Method (SAM2):
-
device: Detector Tube
company: Gastec
part #: 180
range: 1-60 ppm
method classification: Mfg
-
device: Detector Tube
company: MSA
part #: 92115
range: 10-200 ppm
method classification: Mfg
-
device: Detector Tube
company: Kitagawa
part #: 222S
range: 1-20 ppm
method classification: Mfg
-
device: Instrumentation
company: Infrared Spectrophotometer
part #: MIRAN 1A & 1B
range: 1.1 ppm @ 9.0 um
method classification: Mfg
-
device: Instrumentation
company: Infrared Spectrophotometer
part #: MIRAN 103
range: 0-50 ppm @ 8.7 um
method classification: Mfg
-
device: Instrumentation
company: PID
part #: Photoionization Detector
method classification: Mfg
** All Trademarks are the property of their respective owners.
|