Synonyms: Dianisidine; 3,3'-Dianisidine; 3,3'-Dimethoxybenzidine
OSHA IMIS Code Number: D116
Chemical Abstracts Service (CAS) Registry Number: 119-90-4
NIOSH Registry of Toxic Effects of Chemical Substances (RTECS) Identification Number: DD0875000
NIOSH Pocket Guide to Chemical Hazards, o-Dianisidine: chemical description, physical properties, potentially hazardous incompatibilities, and more
National Institute for Occupational Safety and Health (NIOSH) Recommended Exposure Limit (REL): Carcinogen-Lowest Feasible Concentration
Primary Laboratory Sampling/Analytical Method (SLC1):
- sampling media: Polytetrafluoroethylene Filter 5 micron
maximum volume: 500 Liters
maximum flow rate: 3.0 L/min
current analytical method: High Performance Liquid Chromatography; HPLC/UL47
method reference: 1 (NIOSH 5013 [28 KB PDF, 5 pages])
method classification: Fully Validated
note: This method does not differentiate between different o-Dianisidine Dyes. Protect samples from heat & light.
sampling media: Glass Fiber Filter (37 mm)
maximum volume: 100 Liters
maximum flow rate: 1 L/min
current analytical method: High performance liquid chromatography; HPLC/UV/Visible
method reference: 2 (OSHA In-House File)
method classification: Not Validated
note: This method differentiates between different o-dianisidine based dyes. See individual dye of interest. Protect samples from heat & light.
Conditions: Column: C18 Mobile Phase: Detector Wavelength: 280nm Detection Limit: 20.4ug/sample
Wipe Sampling Method:
- sampling media: Glass Fiber Filter
Bulk Method:
- For any dye analysis, a bulk sample of the dye must be sent to the Salt Lake Technical Center. Limit the amount of bulk submitted to one gram or approx. one mL.