    TEXT VERSION OF SLIDE:

    Title: Process Safety Information
    Type: Text Slide
    Content:
    • The facilities PSI Information did not include:
      • Verification of good engineering practices in ammonia system including
        1. Location of the discharge of pressure relief valves (PRVs) for new system
        2. The size of common vent header for PRVs
        3. Suitability of pipe and vessel insulation materials
        4. Installation of PRVs on appropriate devices (#'s 3 and 25 accumulators)
        5. Location of king valves (not operable from floor and no access platform)