| << Return to Previous Page Oxide Drum Filling Local Exhaust Ventilation ![]() Text Version Oxide Drum Filling Local Exhaust Ventilation Oxide drum with drum filling tube, plenum, perforated plate (50% open) or slotted plate (size slot for 2000 fpm), flare fill tube, and flexible tubing to fan or main with 45% take-off. A schematic view is also included. Design Criteria: Q = 600 cfm Vt = 4,500 fpm he = 1.78 VPslot + 0.25 VPduct |